IEEE 485-2020 pdf free.IEEE Recommended Practice for Sizing Lead-Acid Batteries for Stationary Applications.
The loads applied to the battery are normally categorized as constant power, constant resistance, or constant current. However, for sizing purposes, the loads are treated as constant power or constant current. The designer should review each system to be sure all possible loads and their variations are included. If the loads are solely constant power loads, sizing as described in Annex D is appropriate and simplifies the sizing process.
A duty cycle diagram showing the total load at any time during the cycle is an aid in the analysis of the duty cycle. To prepare such a diagram, all loads (expressed in either current or power) expected during the cycle are tabulated along with their anticipated inception and shutdown times. The total time span of the duty cycle is determined by the requirements of the installation.
Loads whose inception and shutdown times are known are plotted on the diagram as they would occur. If the inception time is known, but the shutdown time is indetnite, it should be assumed that the load continues through the renminder of the duty cycle. Similarly, if the shutdown time is known, but the inception is not. it should be assumed that the load begins when the duty profile begins.
Loads that occur at random should be shown at the most critical time of the duty cycle in order to simulate the worst-case load on the battery. These are nonconhinuous or momentary loads as described in 4.2.2 and 4.2.3. To determine the most critical time, it is necessary to size the battery without the random load(s) and to identify the section of the duty cycle that controls battery size. Then the random load(s) should be superimposed on the end of that controlling section as shown in Figure 1 (see 6.4.4).IEEE 485 pdf download.
IEEE 485-2020 pdf free
Note:
Can you help me share this website on your Facebook or others? Many thanks!