AS/NZS 60598.2.23:2021 pdf free.Luminaires Part 2.23: Particular requirements一Extra-low-voltage lighting systems for ELV light sources (IEC 60598-2-23:2020 (ED.2.0) MOD).
The installation instructions shall clearly and unambiguously state:
a) how the extra-low-voltage lighting system is to be mounted, and in particular, the maximum permitted distance between the main supports and the spacing of auxiliary supports;
b) whether special requirements, for example due to characteristics of the transformer/convertor/controlgear, shall be observed for components of an existing mains supply to which the extra- -voltage lighting system is to be connected, for example socket-outlets, switches, dimmers;
C) that the supporting conductors of different extra- -voltage lighting systems shall be mounted so as not to be able to come into contact with each other, where applicable;
d) that the extra- -voltage lighting system shall not be extended beyond the number of luminaires belonging to the complete set, and that only parts assigned by the manufacturer shall be used;
e) that no additional attachments, for example for decorative purposes, shall be used;
f) that the following warning statement be provided:
WARNING o avoid the risk of overheating and fire, do not bridge the conductors;
g) the positions or spacings for the connections of luminaires (if applicable).
23.7 Construction
The provisions of Section 4 of Part 1 apply, together with the requirements of 23.7.1 to 23.7.11.
23.7.1 The whole set of the extra- -voltage lighting system, as delivered by the manufacturer, shall be complete, including the transformer or convertor/controlgear. The secondary side of the extra- -voltage lighting system shall comply with the requirements of
SE LV.
Compliance is checked by mounting as in normal use, inspection and by the applicable measurements and tests required by this document.
23.7.2 Transformers, power supply units or switch mode power supply units provided with safety extra- -voltage lighting systems shall be of the safety isolating type, complying with the requirements of IEC 61558-2-6 or IEC 61558-2-16, and having a rated output voltage not exceeding 25 V RMS or 60 V ripple free DC.
23.7.3 Convertors/controlgear provided with safety extra-low-voltage lighting systems shall be of the safety isolating type, complying with IEC 61347-2-2 or IEC 61347-2-13, and having a rated output voltage not exceeding 25 V RMS or 60 V ripple free DC.
23.7.4 Supporting conductors shall be continuous and shall be capable of supporting five times the mass of the luminaires (including their lamps) intended to be connected to them.
Compliance is checked by applying a load at 900 to the conductors to the mid-point of a maximum span equal to five times the weight of the luminaires and lamps supplied with the system, with a minimum load of 10 kg, for a period of I h, applied simultaneously to both conductors. After the test, the load is removed and the deflection from the normal position shall not exceed 10 % of the distance between the supporting conductors measured before applying the load.
If pin contacts or edge contacts are used in the system, then the supporting conductors shall have been subjected to 25 piercings at different places before the test.
23.7.5 Luminaire connectors shall be capable of supporting five times the mass of the luminaire (including its light source) without permanent deformation.AS/NZS 60598.2.23 pdf free.

Download infomation Go to download
Note: Can you help me share this website on your Facebook or others? Many thanks!
AS/NZS 60079.5:2015 pdf free Free AS Standards

AS/NZS 60079.5:2015 pdf free

AS/NZS 60079.5:2015 pdf free.Explosive atmospheres Part 5: Equipment protection by powdered filling 'q'. 4.1.1.3 Containers intended to be opened for repair Electrical equipment, parts of electrical equipment, or Ex components that are designed to be repaired shall...
Get More
AS/NZS 60079.2:2015 pdf free Free AS Standards

AS/NZS 60079.2:2015 pdf free

AS/NZS 60079.2:2015 pdf free.AUSTRALIAN/NEW ZEAL AND STANDARD Explosive atmospheres. 5 Constructional requirements for pressurized enclosures 5.1 Enclosure The pressurized enclosure shall have a degree of protection in accordance with Table 2. For Level of Protection pxb with...
Get More
AS/NZS 5263.1.3:2016 pdf free Free AS Standards

AS/NZS 5263.1.3:2016 pdf free

AS/NZS 5263.1.3:2016 pdf free.Gas appliances Part 1.3: Gas space heating appliances. 2.1 SCOPE This Clause of AS 5263.0 applies. 2.2 GENERAL DESIGN REQUIREMENTS This Clause of AS 5263.0 applies, except as modified below. 2.2.13 IJesign olappliance base...
Get More

LEAVE A REPLY

Anonymous netizen Fill in information