5.1.4 Tolerances
5.1.4.1 Unless otherwise stated, the tolerances for the environmental test parameters shall be as given in the basic reference standards for the test (e.g. the relevant part of IEC 60068).
5.1.4.2 If a specific tolerance or deviation limit is not specified in a requirement or test procedure, then a deviation limit of ±5 % shall be applied.
5.1.5 Measurement of CO response value
5.1.5.1 Install the specimen for which the CO response value Is to be measured in a gas test chamber, as specified in Annex A, in its normal operating position, by its normal means of attachment. The orientation of the specimen, relative to the direction of gas flow, shall be the least sensitive orientation as determined in the directional dependence test (see 5.3), unless otherwise specified in the test procedure.
5.1.5.2 Purge the gas test chamber to ensure that the carbon monoxide concentration is less than 1 iLl/I prior to each test.
5.1.5.3 The air velocity in the proximity of the specimen shall be (0,2 ± 0,04) rn/s during the measurement, unless otherwise specified in the test procedure.
5.1.5.4 Unless otherwise specified in the test procedure, the air temperature in the gas test chamber shall be (23 ± 5) °C and shall not vary by more than 5 K for all the measurements on a particular detector type.
5.1.5.5 Connect the specimen to its supply and monitoring equipment as specified in 5.1.3, and allow it to stabilize for a period of at least 15 mm, unless otherwise specified by the manufacturer.
5.1.5.6 For detectors whose response is rate sensitive, the manufacturer may specify a rate of increase within this range to ensure that the measured response value is representative of the static response value of the detector. The rate of increase in CO concentration shall be similar for all measurements on a particular detector type.
5.1.5.7 Introduce carbon monoxide gas at a rate of between I iil/l/min and 6 il/I/mm until the specimen has entered an alarm state. For detectors whose response is rate sensitive, the manufacturer may specify a rate of increase within this range to ensure that the measured response value is representative of the static response value of the detector.
NOTE To avoid unnecessary high levels of CO. the test can be stopped when the CO concentration reaches 100 p1/I.
5.1.5.8 The rate of increase in CO concentration shall be similar for all measurements on a particular detector type.
5.1.5.9 Record the carbon monoxide concentration at the moment the specimen gives an alarm. This shall be taken as the CO response value, S.
5.1.6 Measurement of heat sensor response value
5.1.6.1 Where detectors comply with ISO 7240-5, the response times measured in those tests may be used as the heat response values for the purposes of this part of ISO 7240.
5.1.6.2 Install the specimen for which the temperature response value is to be measured in a heat tunnel, as specified in Annex B. in its normal operating position, by its normal means of attachment.AS ISO 7240.8 pdf download.

Download infomation Go to download
Note: Can you help me share this website on your Facebook or others? Many thanks!
AS/NZS 60079.5:2015 pdf free Free AS Standards

AS/NZS 60079.5:2015 pdf free

AS/NZS 60079.5:2015 pdf free.Explosive atmospheres Part 5: Equipment protection by powdered filling 'q'. 4.1.1.3 Containers intended to be opened for repair Electrical equipment, parts of electrical equipment, or Ex components that are designed to be repaired shall...
Get More
AS/NZS 60079.2:2015 pdf free Free AS Standards

AS/NZS 60079.2:2015 pdf free

AS/NZS 60079.2:2015 pdf free.AUSTRALIAN/NEW ZEAL AND STANDARD Explosive atmospheres. 5 Constructional requirements for pressurized enclosures 5.1 Enclosure The pressurized enclosure shall have a degree of protection in accordance with Table 2. For Level of Protection pxb with...
Get More
AS/NZS 5263.1.3:2016 pdf free Free AS Standards

AS/NZS 5263.1.3:2016 pdf free

AS/NZS 5263.1.3:2016 pdf free.Gas appliances Part 1.3: Gas space heating appliances. 2.1 SCOPE This Clause of AS 5263.0 applies. 2.2 GENERAL DESIGN REQUIREMENTS This Clause of AS 5263.0 applies, except as modified below. 2.2.13 IJesign olappliance base...
Get More

LEAVE A REPLY

Anonymous netizen Fill in information