AS 1735.5.2:2019 pdf download.Lifts, escalators and moving walks Part 5.2: Safety of escalators and moving walks一Rules for the improvement of safety of existing escalators and moving walks (EN 115-2:2017, MOD).
5 Safety requirements and/or protective measures
5.1 General
The following requirements and/or protective measures shall not be considered as the only possible solution. Alternatives are permitted, provided they lead to an equivalent safety level.
A risk assessment shall be made on a case by case basis to identify hazards or hazardous situations not covered in this standard.
Where the requirements of this standard cannot be met technically and a residual risk remains, or cannot be avoided, the level of nsk shall be reduced as far as it is practicable. When residual risk remains the use of appropriate procedures such as signs, instructions and training should be considered.
Harmful materials such as asbestos in brake linings. contactor shields, cladding including machinery spaces and separate machine rooms or control cabinet locations, etc. shall be replaced by materials which ensure the same performance level.
NOTE These should be considered in relation to national requirements.
For specific requirements such as accessibility, the conditions in the building shall be assessed to determine what is practical to be applied for escalators and moving walks.
If an escalator or moving walk has been upgraded by one of the measures described in this standard, the consequences to other parts of the escalator or moving walk shall be considered with special regard to
EN 1 15-1:2008+A1:2010.
5.2 Supporting structure (truss) and enclosure
5.2.1 General
All mechanically moving parts of the escalator or moving walk shall be completely enclosed within panels or walls. Exempt from this are the accessible steps, the accessible pallets, the accessible belt and that part of the handrail available for the user. Ventilation apertures in compliance with EN ISO 13857:2008, Table 5 are permitted.
Exterior panels which are designed to be opened (e.g. for cleaning purposes), inspection covers and floor plates shall be provided with an electric safety device according to EN 115-1:2008+A1:2010, Table 6 n). For inspection covers and floor plates it shall only be possible to open them by a key or a tool suited for that purpose.
If rooms behind inspection covers and floor plates can be entered, it shall be possible to open them from the inside without a key or a tool even when locked.
It is permissible to omit an enclosure of the mechanically moving parts if other measures (such as rooms with locked doors accessible to authorised personnel only) make a hazard to the public impossible.
5.2.2 Fire hazard
5.2.2.1 Accumulation of combustible material inside the truss due to the daily environmental pollution can generate a fire hazard. Therefore, the inner part of the escalator/moving walk shall be cleaned regularly.
5.2.2.2 Depending on the maintenance conditions. e.g. access, fire protection systems shall be installed.
5.3 Steps, pallets and belt
5.3.1 Tread surfaces for escalators and moving walks shall provide a secure footloId taking into consideration the operational and environmental conditions.
5.3.2 Demarcation (e.g. groove in the step tread) shall be provided to highlight at the landings the rear edge of the steps.AS 1735.5.2 pdf download.

Download infomation Go to download
Note: Can you help me share this website on your Facebook or others? Many thanks!
AS/NZS 60079.5:2015 pdf free Free AS Standards

AS/NZS 60079.5:2015 pdf free

AS/NZS 60079.5:2015 pdf free.Explosive atmospheres Part 5: Equipment protection by powdered filling 'q'. 4.1.1.3 Containers intended to be opened for repair Electrical equipment, parts of electrical equipment, or Ex components that are designed to be repaired shall...
Get More
AS/NZS 60079.2:2015 pdf free Free AS Standards

AS/NZS 60079.2:2015 pdf free

AS/NZS 60079.2:2015 pdf free.AUSTRALIAN/NEW ZEAL AND STANDARD Explosive atmospheres. 5 Constructional requirements for pressurized enclosures 5.1 Enclosure The pressurized enclosure shall have a degree of protection in accordance with Table 2. For Level of Protection pxb with...
Get More
AS/NZS 5263.1.3:2016 pdf free Free AS Standards

AS/NZS 5263.1.3:2016 pdf free

AS/NZS 5263.1.3:2016 pdf free.Gas appliances Part 1.3: Gas space heating appliances. 2.1 SCOPE This Clause of AS 5263.0 applies. 2.2 GENERAL DESIGN REQUIREMENTS This Clause of AS 5263.0 applies, except as modified below. 2.2.13 IJesign olappliance base...
Get More

LEAVE A REPLY

Anonymous netizen Fill in information