AS 1603.3-2018 pdf free download.Australian Standard Automatic fire detection and alarm systems Part 3: Heat alarms.
4.4 Alarm condition
4.4.1 Alarm condition audible indicator
4.4. 1. 1 Signal pattern
The alarm signal pattern shall be in accordance with either ISO 8201 or ISO 7731.
4.4. 1 .2 Signal pattern Ic vel—Optional function
Where this function is provided, the alarm condition aural signal pattern shall commence sounding at a level not greater than 45 dBA and rise gradually to the maximum level of not more than 105 dBA over a period of between 3 s to 12 s (see Clause 5.16).
4.4. 1 .3 Signal pattern frequency characteristics —Optional function
Where this function is provided, the signal pattern shall have a fundamental frequency of 520 Hz with odd harmonics to approximate a square wave.
4.4.2 Alarm con(Iitiofl visual indicator
Heat alarms shall be provided with an integral visual alarm indicator, by which the individual heat alarm, when in alarm condition, can be identified. The visual alarm indicator shall be red in the alarm condition. The indicator shall flash or be continuously illuminated when the alarm condition is present.
Visual alarm indicators shall not operate on interconnected heat alarms that have not reached their response threshold (Ath). This visual alarm indicator may also perform other additional functions, provided the alarm indication is distinct from any additional function. The failure of any visual alarm condition indicator shall not prevent the alarm condition.
4.5 Main power source visual indicator
A heat alarm intended for connection to the external main power source shall be provided with a visual indicator. The indicator shall be continuously illuminated when the power source is present. The indicator shall be green when lit, hut may extinguish in the alarm condition. The failure of any visual condition indicator shall not prevent the alarm condition.
4.6 Fault condition visual indicator—Optional function
Where this function is provided, the following requirements apply.
The heat alarm shall be provided with an integral visual fault condition indicator that is amber or yellow when lit. The indicator shall flash or be continuously illuminated when the fault condition is present. The indicator may be combined with the alarm condition visual indicator provided the fault visual indicator is suppressed during the alarm condition. The failure of any visual fault condition indicator shall not prevent the alarm condition.
4.7 Heat alarm signals—Requirements for heat alarms with additional features
The following requirements apply to heat alarms that employ features in addition to those
required by this Standard:
(a) The alarm condition shall take precedence over any other signal, even when such other signal is initiated first.
(b) The alarm signal shall be distinctive from the signals of non-alarm condition functions.
NOTE: A common sounder may be used, provided distinctive signals are obtained.AS 1603.3 pdf download.

Download infomation Go to download
Note: Can you help me share this website on your Facebook or others? Many thanks!
AS/NZS 60079.5:2015 pdf free Free AS Standards

AS/NZS 60079.5:2015 pdf free

AS/NZS 60079.5:2015 pdf free.Explosive atmospheres Part 5: Equipment protection by powdered filling 'q'. 4.1.1.3 Containers intended to be opened for repair Electrical equipment, parts of electrical equipment, or Ex components that are designed to be repaired shall...
Get More
AS/NZS 60079.2:2015 pdf free Free AS Standards

AS/NZS 60079.2:2015 pdf free

AS/NZS 60079.2:2015 pdf free.AUSTRALIAN/NEW ZEAL AND STANDARD Explosive atmospheres. 5 Constructional requirements for pressurized enclosures 5.1 Enclosure The pressurized enclosure shall have a degree of protection in accordance with Table 2. For Level of Protection pxb with...
Get More
AS/NZS 5263.1.3:2016 pdf free Free AS Standards

AS/NZS 5263.1.3:2016 pdf free

AS/NZS 5263.1.3:2016 pdf free.Gas appliances Part 1.3: Gas space heating appliances. 2.1 SCOPE This Clause of AS 5263.0 applies. 2.2 GENERAL DESIGN REQUIREMENTS This Clause of AS 5263.0 applies, except as modified below. 2.2.13 IJesign olappliance base...
Get More

LEAVE A REPLY

Anonymous netizen Fill in information