IEC 61000-3-3-2021 pdf free Limitation of voltage changes

06-23-2021 comment

IEC 61000-3-3-2021 pdf free.Electromagnetic compatibility (EMC) – Part 3-3: Limits – Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems, for equipment with rated currents 16 A per phase and not subject to conditional connection.
This part of IEC 61000 is concerned with the limitation of voltage fluctuations and flicker impressed on the public low-voltage system.
It specifies limits of voltage changes which may be produced by an equipment tested under specified conditions and gives guidance on methods of assessment.
This part of lEG 61000 is applicable to electrical and electronic equipment having an input current equal to or less than 16 A per phase. intended to be connected to public low-voltage distribution systems of between 220 V and 250 V line to neutral at 50 Hz, and not subject to conditional connection.
Equipment which does not comply with the limits of this part of lEG 61000 when tested with the reference impedance Zret of 6.4, and which therefore cannot be declared compliant with this part, may be retested or evaluated to show conformity with IEC 61000-3-11. Part 3-11 is applicable to equipment with rated input current < 75 A per phase and subject to conditional connection.
The tests according to this part are type tests. Particular test conditions are given in Annex A and the test circuit is shown in Figure 1.
NOTE I The limits in this standard relate to the voltage changes experienced by consumers connected at the Interface between the public supply low-voltage network and the equipment user’s Installation. Consequently, If the actual impedance of the supply at the supply terminals of equipment connected within the equipment users installation exceeds the test impedance, it is possible that supply disturbance exceeding the limits could occur.
NOTE 2 The limits In this standard are based mainly on the subjective severity of flicker imposed on the light from 230 V 60 W coiled-coil filament lamps by fluctuations of the supply voltage. For systems with nominal voltage less than 220 V line to neutral and/or frequency of 60 Hz, the limits and reference circuit values are under consideration.
2 NormatIve references
The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC/TR 60725, Consideration of reference impedances and public supply impedances for use in determining disturbance characteristics of electrical equipment having a rated current < 75 A per phase
lEG 60974-1. Arc welding equipment — Part 1: Welding power sources
IEC 61 000-3-2. Electromagnetic compatibility (EMC) — Part 3-2: Limits — Limits for harmonic current emissions (equipment in put current < 16 A per phase)IEC 61000-3-3 pdf download.

Download infomation Go to download
Note: Can you help me share this website on your Facebook or others? Many thanks!

LEAVE A REPLY

Anonymous netizen Fill in information