IEC 60331-2-2018 pdf free download

07-16-2021 comment

IEC 60331-2-2018 pdf free download.Tests for electric cables under fire conditions – Circuit integrity – Part 2: Test method for fire with shock at a temperature of at least 830。C for cables of rated voltage up to and including 0,6/1,0 kV and with an overall diameter not exceeding 20 mm.
This part of IEG 60331 specifies the test method for cables which are required to maintain circuit integrity when subject to tire and mechanical shock under specified conditions.
This document is applicable to cables of rated voltage not exceeding 600 v/i 000 V, including those of rated voltage below 80 V. metallic data and telecom cables and optical fibre cables.
It is intended for use when testing cables of not greater than 20 mm overall diameter.
Cables of larger diameter are intended to be tested using the apparatus, procedure and requirements of IEC 60331-1.
This document includes details for the specific point of failure, continuity checking arrangement, test sample, test procedure and test report relevant to electric power and control cables with rated voltage up to and including 600 V/i 000 V. Details for the specific point of failure, continuity checking arrangement, test sample. test procedure and test report relevant to metallic data and telecom cables and optical fibre cables are not given by
IEC 60331-2.
Although the scope is restricted to cables with rated voltage up to and including 0,6/1,0 kV, the procedure can be used, with the agreement of the manufacturer and the purchaser, for cables with rated voltage up to and including 1,8/3 (3.3) kV. provided that suitable fuses are used.
Annex A provides the method of verification of the burner and control system used for the test.
Requirements are stated for an identification that may optionally be marked on the cable to signify compliance with this standard.
CAUTION — The test given in this standard may Involve the use of dangerous voltages and temperatures. Suitable precautions should be taken against the risk of shock, burning, fire and explosion that may be involved, and against any noxious fumes that may be produced.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC 60584-1,Thermocouples – Part 1: EMF specifications and tolerances
IEC 60269-3, Low-voltage fuses — Part 3: Supplementary requirements for fuses for use by unskilled persons (fuses mainly for household and similar applications) — Examples of standardized systems of fuses A to F
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
• lEG Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http:J/www.iso.orglobp
3.1 circuit Integrity
ability of an electric cable to continue to operate in the designated manner whilst subjected to
a specified flame source for a specified period of time under specified conditions
3.2 draught-free environment
space in which the results of tests are not significantly affected by the local air speed
4 Test environment
The test shall be carried out in a draught-free environment within a suitable chamber, of minimum volume 20 m3, with facilities for disposing of any noxious gases resulting from the burning. Sufficient ventilation shall be available to sustain the flame for the duration of the test. Air inlets and the exhaust chimney should be located in such a way that the burner flame remains stable during the verification procedure and test. If necessary. the burner shall be shielded from any draughts by the use of draught shields. Windows may be installed in the walls of the chamber in order to observe the behaviour of the cable during the test. Fume exhaust should be achieved by means of natural draught through a chimney located at least 1 m from the burner. A damper may be used for adjustment of ventilation conditions.
NOTE Experience has shown a chamber similar to the 3 m cube specified in IEC 61034-1 to be suitable.
The chamber and test apparatus shall be at a temperature of between 10 °C and 40 °C at the start of each test.
The same ventilation and shielding conditions shall be used in the chamber during both the verification and cable test procedures.IEC 60331-2 pdf download.

Download infomation Go to download