AS 7240.12:2018 pdf free.Fire detection and alarm systems Part 12: Line type smoke detectors using a transmitted optical beam (ISO 7240-12:2014, MOD).
4.5 Manufacturer’s adjustments
It shall not be possible to change the manufacturer’s settings except by special means (e.g. the use of a
special code or tool) or by breaking or removing a seal.
4.6 On-site adjustment of response threshold value
4.6.1 If there is provision for on-site adjustment of the response threshold value of the detector then
a) for all of the settings at which the manufacturer claims compliance, the detector shall comply with the requirements of this part of ISO 7240 and access to the adjustment means shall be possible only by the use of a code or special tool or by removing the detector from its base or mounting;
b) any setting or settings at which the manufacturer does not claim compliance with this part of ISO 7240 shall be accessible only by the use of a code or special tool, and it shall be clearly marked on the detector or in the associated data that if these setting or settings are used, the detector does not comply with this part of ISO 7240.
4.6.2 These adjustments may be carried out at the detector or at the fire detection control and indicating equipment.
4.7 Protection of optical components
The detector shall be so designed that a sphere of dianwter greater than (1,3 ± 0,05) mm cannot pass into any enclosure containing optical components when the detector is in the operational condition.
NOTE This requirement is intended to restrict the access of insects into the sensitive parts of the detector. It is known that this requirement Is not sufficient to prevent the access of all insects, therefore, it may be necessary to take other precautions against unwanted alarms due to the entry of small insects.
4.8 Limit of compensation
4.8.1 Compensation may be used to mitigate changes in sensitivity due to the build-up of dust and other contaminants on the optical surfaces (see Annex A).
4.8.2 The detector shall emit either a fault or alarm signal at the limit of compensation for the effect of a slowly changing signal response.
4.8.3 Since it is practically impossible to perform tests with very slight increases in attenuation, an evaluation of the detectors conformity shall be made by analysing the circuits/software and/or by physical tests and simulations.
4.9 Fault signalling
A fire alarm signal shall not be cancelled by a fault resulting from a rapid change in obscuration (in accordance with 5) or by a result of the limit olcompensation being reached (in accordance with 4k).AS 7240.12 pdf download.

Download infomation Go to download
Note: Can you help me share this website on your Facebook or others? Many thanks!
AS/NZS 60079.5:2015 pdf free Free AS Standards

AS/NZS 60079.5:2015 pdf free

AS/NZS 60079.5:2015 pdf free.Explosive atmospheres Part 5: Equipment protection by powdered filling 'q'. 4.1.1.3 Containers intended to be opened for repair Electrical equipment, parts of electrical equipment, or Ex components that are designed to be repaired shall...
Get More
AS/NZS 60079.2:2015 pdf free Free AS Standards

AS/NZS 60079.2:2015 pdf free

AS/NZS 60079.2:2015 pdf free.AUSTRALIAN/NEW ZEAL AND STANDARD Explosive atmospheres. 5 Constructional requirements for pressurized enclosures 5.1 Enclosure The pressurized enclosure shall have a degree of protection in accordance with Table 2. For Level of Protection pxb with...
Get More
AS/NZS 5263.1.3:2016 pdf free Free AS Standards

AS/NZS 5263.1.3:2016 pdf free

AS/NZS 5263.1.3:2016 pdf free.Gas appliances Part 1.3: Gas space heating appliances. 2.1 SCOPE This Clause of AS 5263.0 applies. 2.2 GENERAL DESIGN REQUIREMENTS This Clause of AS 5263.0 applies, except as modified below. 2.2.13 IJesign olappliance base...
Get More

LEAVE A REPLY

Anonymous netizen Fill in information