AS 61534.1:2020 pdf download.Powertrack systems Part 1: General requirements (IEC 61 534-1:201 1+AMD1:2014 CSV (ED. 2.1) MOD).
7.3 According to degrees of protection provided by enclosures according to IEC 60529.
7.3.1 According to protection against ingress of solid foreign objects.
7.3.2 According to protection against ingress of water.
7.4 According to degree of pollution
7.4.1 Pollution degree 1
7.4.2 Pollution degree 2
7.4.3 Pollution degree 3
NOTE 1 Details for the pollution degrees are given in Annex D.
NOTE 2 A PT system suitable for use in a particular situation may be used in a less polluted situation.
7.5 According to the rated impulse withstand voltage:330V,500V,1500V,2500V,4000V.
NOTE The relationship between rated impulse withstand voltage, rated voltage and overvoltage category is given in Annex C
8 Marking and documentation
8.1 Each system component shall be marked with
a) the name or trademark of the manufacturer or responsible vendor;
b) product identification which may comprise, for example, a colour, a catalogue number, a symbol.
In the case where the PT system is supplied as an assembly then only the assembly need be marked, and this shall not be on easily removable parts.
Where it is not possible to mark a component due to its size, then it will be sufficient to mark the smallest package unit according to 8.1.
Compliance is checked by inspection.
8.2 In addition to 8.1 the powertrack, tap-off units and supply connectors shall be marked with
a) rated voltage in volt,
b) rated current in ampere,
C) nature of supply e.g. 50Hz, 60 Hz.
If symbols are used, they shall be in accordance with 8.7.
Compliance is checked by inspection.
8.3 Line, neutral and earth terminals for external conductors shall be marked using me symbols in accordance with 8.7; alternatively these marks can be placed adjacent to the terminal.
Compliance is checked by inspection.
8.4 If necessary for correct installation, for example for screwless type or insulation piercing terminals, the following information shall be given by marking adjacent to terminals:
— connection and disconnection procedure;
— cross-sectional areas and types of connectable conductors.
NOTE Type of connectable conductors could include solid, stranded, flexible, copper or amirnum.
Alternatively the information may be given on the smallest package unit or in the manufacturer’s installation instructions.
In addition, the location of protective devices such as fuses, circuit breakers and residual current devices which are not visible after installation shall be marked in their vicinity with the appropriate symbol or text which shall be visible after installation. In the case of fuses or other protective devices which can be replaced without the use of a tool, the appropriate current shall also be marked and if necessary, the appropriate voltage.
Compliance is checked by inspection.
8.5 The manufacturer or responsible vendor shall provide documentation giving the information necessary for the proper and safe installation and use of the PT system for
— system components of the PT system:
— the purpose of the system components and their assemblies;
— the classification of the PT system according to Clause 7;
— guidance to reach the declared performance;
— guidance regarding periodic inspection and/or maintenance where required;
— static loading characteristics (see 14.3), if any.AS 61534.1 pdf download.

Download infomation Go to download
Note: Can you help me share this website on your Facebook or others? Many thanks!
AS/NZS 60079.5:2015 pdf free Free AS Standards

AS/NZS 60079.5:2015 pdf free

AS/NZS 60079.5:2015 pdf free.Explosive atmospheres Part 5: Equipment protection by powdered filling 'q'. 4.1.1.3 Containers intended to be opened for repair Electrical equipment, parts of electrical equipment, or Ex components that are designed to be repaired shall...
Get More
AS/NZS 60079.2:2015 pdf free Free AS Standards

AS/NZS 60079.2:2015 pdf free

AS/NZS 60079.2:2015 pdf free.AUSTRALIAN/NEW ZEAL AND STANDARD Explosive atmospheres. 5 Constructional requirements for pressurized enclosures 5.1 Enclosure The pressurized enclosure shall have a degree of protection in accordance with Table 2. For Level of Protection pxb with...
Get More
AS/NZS 5263.1.3:2016 pdf free Free AS Standards

AS/NZS 5263.1.3:2016 pdf free

AS/NZS 5263.1.3:2016 pdf free.Gas appliances Part 1.3: Gas space heating appliances. 2.1 SCOPE This Clause of AS 5263.0 applies. 2.2 GENERAL DESIGN REQUIREMENTS This Clause of AS 5263.0 applies, except as modified below. 2.2.13 IJesign olappliance base...
Get More

LEAVE A REPLY

Anonymous netizen Fill in information